What is the phenomenon of partial discharge in dry-type transformers?

2018-03-30 15:00

Partial discharge mainly occurs in dry-type transformers, transformers, and other high-voltage electrical equipment when they are subjected to high voltage. Inside these devices, insulation experiences discharge. This discharge only occurs in a localized area of the insulation and does not immediately result in a complete breakdown or flashover of the entire insulation. Therefore, it is called partial discharge. The partial discharge quantity is very weak and cannot be detected by human intuition through visual observation and auditory perception. Only highly sensitive partial discharge measurement instruments can detect it.

The internal insulation of dry-type transformers remains under the action of working voltage for a long time during operation. Especially as the voltage level increases, the electric field strength that the insulation has to withstand becomes very high. In weakly insulated areas, local discharge is prone to occur. The reasons for local discharge are as follows: the electric field is overly concentrated at a certain point, or the electric field strength at a certain point is too high. For example, if there are bubbles in the solid medium or impurities have not been removed completely; if there is water, gas or suspended particles in the oil; or in different medium combinations, there is severe electric field distortion at the interface. The traces of local discharge on the solid insulation often leave only a small spot or a branch-like burn mark. In the oil, some small gas bubbles are formed.

Although the duration of partial discharge is short and the energy is small, it poses great danger. Its long-term existence will cause significant damage to the insulating materials. Firstly, the insulating materials adjacent to the partial discharge will be directly bombarded by the discharge particles, resulting in local insulation damage. Secondly, the chemical effects of active gases such as heat, ozone, and nitrogen oxide generated by the discharge will corrode and age the local insulation, increasing the electrical conductivity, and ultimately leading to thermal breakdown. In operating dry-type transformers, the aging and damage of the internal insulation often start from partial discharge.

The detection methods for partial discharge in transformers are generally as follows:

1. Electrical testing method. Use an oscilloscope or radio interference detector to identify the characteristic waveforms of the discharge or the degree of radio interference.

2. Ultrasonic measurement method. Detect the sound waves generated during the discharge process, convert the sound waves into electrical signals, record them on a tape for analysis. By utilizing the time difference in the transmission of electrical signals and sound signals, the distance from the detection point to the discharge point can be calculated.

3. Chemical testing method. This method measures the content of various dissolved gases in the oil and their changing patterns. It can detect the composition, proportion and quantity changes in the oil, thereby determining whether there is local discharge (or local overheating).

In addition, in recent years, online detection instruments for partial discharge have also been developed, which can automatically detect partial discharge during the operation of transformers.

To prevent the occurrence of partial discharge, the manufacturing unit should conduct a reasonable structural design for the dry-type transformer; carry out meticulous construction, improve the purity of materials, and strictly control the quality at all stages. The operating unit should strengthen the maintenance and monitoring of the dry-type transformer to effectively prevent the occurrence of partial discharge in the transformer.